A new installation for the Chausey islands

A bit of marine freshness 🌬️ for our return to work with the installation of this fourth production genset for the Chausey Islands!

This P275-5 FG Wilson genset has been modified by our technical team in the workshop with:
- Modification of the oil system (change of the engine heater for a less powerful one, addition of an automatic oil top-up, addition of an oil separator to recover the oil and reinject it in the circuit, addition of an oil tank)
- Addition of an automatic fuel transfer pump
- Installation of a retention tank
- Replacement of the AVR to vary the power according to the needs of the network
- Replacement of the control module with a DSE7410 to retrieve all the parameters of the genset on the supervision in Modbus TCP IP
- Addition of a PMG to allow a better recovery of the network impacts
- Installation of a motorised circuit breaker for synchronisation with the 3 other gensets
- Cutting for the passage of an inlet and outlet air duct, and filling of the other air passages

Modifications, delivery and installation in less than a month for this production genset ⚡
en_USEnglish
GeniWatt
Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.